Nexans ALSECURE FIL H07Z1-U 1X1.5 NR R100
Nexans ALSECURE FIL H07Z1-U 1X1.5 NR R100
Nexans ALSECURE® H07Z1-U / H047Z1-R type 2 wires are not only halogen free (SA, SD) and flame retardant (F1), they are also fire retardant (F2).
Read more- Nexans ref. : 10270106
- Country ref. : 01272972
- EAN : 3427500031100
Description
Description
Standards
-
ProductEN 50525-3-31
Application
- Halogenfree insulated conductors for fixed installations
- For domestic and industrial applications as well as for panel wiring
Design
- Copper core, solid (U) or stranded (R)
- Halogen free insulating sheath (SA and SD according to art.104 of the RGIE/AREI) with F2 characteristic
Installation
- In industries
- In houses
- Open-air laying : with protection
- Ground laying : with protection
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor shape
Circular
Conductor flexibility
Solid class 1
Insulation
Halogen-free
Halogen free
NBN C30-004 ST,SD,SA
Sheath colour
-
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
1.5 mm²
Average insulation thickness
0.7 mm
Minimum outer diameter
2.6 mm
Maximum outer diameter
3.2 mm
Approximate weight
21 kg/km
Nominal outer diameter
2.8 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
450/750 V
Permissible current rating in open air
18 A
Voltage drop, single phase
24.2 V/A.km
Characteristic impedance
- Ohm
Mechanical characteristics
Mechanical characteristics
Impact resistance Max (IEC 30364-5-51)
- J
Usage characteristics
Usage characteristics
Bending factor when laying
4 (xD)
Field of application
Indoor
Flame retardant
NBN C30-004-F1
Fire retardant
NBN C 30-004-F2
Operating temperature, range
-5 ... 60 °C
Resistance to vibrations
Moderate
Chemical resistance
Medium
Packaging
Coil
Length
- m
Resources
Resources
Selling & delivery Information
- Type 2 = fire retardant according to IEC 60332-3-24 and F2 according NBN C30-004.
- Other colours available upon request
Declaration of Performance
- Declaration of Performance n� : 1000263-FRAU
- Certification Date : 7/12/17
- AVCP (Assessment and Verification of Constancy of Performance) : System 1+
- Notified body : NB 2658
- Declared performance : Cca-s1,d1,a1
Our websites