Nexans ALSECURE® 4G35 Cca-s1,d1,a1

Description

Description

Standards

  • Product
    IEC 60228; NF C32-323; NF C32-323
  • Installation
    NF C15-100; NF C15-100

Application

Nexans ALSECURE® Cca cables are designed to be used in private residences or public areas, in all premises open to the public and industries, for power and control circuits.
Nexans ALSECURE® Cca cables are fire retardant, low smoke and halogen free. In the event of fire, emitted gases are non corrosive and have a very low toxicity.

Installation

Nexans ALSECURE® Cca cables will be installed in accordance with the current regulation. 
In case of laying operation between 0°C and -10°C, warm up the cables in a heated room 48 hours minimum before installation.

Nexans ALSECURE® Cca  cables are not designed for buried installation.

Fire performance

  • Fire retardant: EN50399
  • Flame retardant: EN60332-1-2
  • Halogen free: IEC 60754-2

 

Description

Conductor
Solid bare copper class 1 for cross-sections 1,5mm², 2.5mm² and 4mm²
Stranded bare copper class 2 for other sections
Also available in class 2 for cross-sections 1,5mm², 2.5mm² and 4mm²

Insulation
Cross-linked polyethylene (XLPE)

Assembling
Inner sheath acting as a filler

Outer sheath
Halogen free polyolefin
Colour: green 

Marking

 ALSECURE FR-N1 X1G1-R or U Nber of conductor & cross-section 0.6/1kV NF-USE NEXANS 279 WW YYYY Cca-s1, d1, a1 Manufacturing n° DoP:1000361-FRME + metric marking

 

"NF-USE" marking is not applicable for cables that are not described in NF C 32-323.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2
Conductor material
Bare copper
Insulation
XLPE (Cross-linked Polyethylene)
Outer sheath
Halogen free polyolefin
Sheath colour
Green
Halogen free
IEC 60754-1
Conductor shape
Circular
Higher heating value
- MJ/km
With Green/Yellow core
Yes
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Neutral conductor section (when smaller)
- mm²
Minimum outer diameter
23.0 mm
Maximum outer diameter
28.5 mm
Number of cores
4
Conductor cross-section
35 mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 60 °C
Gases corrosivity
IEC 60754-2
Smoke density
EN 50399
Flame retardant
NFC 32070 C2, IEC 60332-1-2
Fire retardant
NF C 32-070 C1, IEC 60332-3-24 (cat.C)
Water proof
Good
U.V resistance
AN2
Max. conductor temperature in service
90 °C
Standard
Cable standardized

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000361-FRME
  • Certification Date : 12/20/22
  • AVCP (Assessment and Verification of Constancy of Performance) : System 1+
  • Notified body : 2658
  • Declared performance : Cca-s1,d1,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close