- Markets
- Products
- Services
- Newsroom
- Tools & Resources
- About Nexans
- Search
- Contact us
- Compare
- Sign in
(N)HX4GAF 1x4 Brown
Description
Description
Standards
-
ProductDIN VDE 0282; DIN VDE 0282; EN 50525-2-42; Nexans specification
Application
Heat resistant, zero halogen insulated wires
Design
1. Conductor
Stranded copper wires tinned
Class 5
DIN VDE 0295
2. Insulation
Special crosslinked elastomer EI3
DIN VDE 0282 Part 7
Colour :
Red - Green/Yellow - Blue - White - Brown - Black - Yellow - Orange - Purple
Section 0.75mm² and 1mm² on request
Marking
Nexans AX VDE-REG.NR. 9577 (N)HX4GAF Max.120°C
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Bare and tinned copper
Halogen free
IEC 60754-1
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
4 mm²
Nominal outer diameter
4.5 mm
Minimum outer diameter
4.4 mm
Maximum outer diameter
4.6 mm
Electrical characteristics
Electrical characteristics
Maximum permissible nominal current
36 A
Rated Voltage Uo/U (Um)
450/750 V
Max. DC resistance of the conductor at 20°C
5.09 Ohm/km
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Flexible
Usage characteristics
Usage characteristics
Flame retardant
IEC 60332-1
Smoke density
IEC 61034
Gases corrosivity
IEC 60754-2
Packaging
Box
Max. conductor temperature in service
120 °C
Short-circuit max. conductor temperature
250 °C
Ambient static operating temperature, range
-30 ... 110 °C
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania