Nexans U-1000 ARVFV 3x95+50

Description

Description

Standards

  • Product
    NF C32-013; XP C 32-322
  • International
    IEC 60298

Application

Nexans U-1000 ARVFV armoured aluminium cables can be used in all low voltage power installations.
 

 

Installation

These cables are suitable for direct burial without additionnal protection , for installation on cables trays or in conducts where mechanical protection is necessary (bursting risk).

 

Design

  • Conductor : stranded circular aluminium class 2
  • Insulation : XLPE- cores identification by colours
  • Laying up : with fillers
  • Inner sheat : lead free PVC
  • Armour : steel or aluminium tapes
  • Outer sheath : Lead free black PVC 

Construction according to AD8 is possible on request.

 

Marking

U-1000 ARVFV NF-USE N° factory S.Y+  N (x or G) S mm²

  • N = number of cores
  • S = section in mm²
  • x = without Green-Yellow
  • G = with Green-Yellow

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor flexibility
Stranded class 2
Insulation
XLPE (chemical)
Inner sheath
PVC
Armour type
Steel tapes
Outer sheath
PVC
Sheath colour
Black
Lead free
Yes
Conductor shape
Circular
With Green/Yellow core
No
With smaller neutral conductor
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Conductor cross-section
95 mm²
Neutral conductor section (when smaller)
50 mm²
Nominal outer diameter
41.1 mm
Approximate weight
2846 kg/km
Bare wire diameter
11.2 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Permissible current rating in open air
227 A
Permissible current rating when buried
234 A
Max. DC resistance of the conductor at 20°C
0.32 Ohm/km
Voltage drop, 3 conductors
0.64 V/A.km
Voltage drop, single phase
- V/A.km

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Excellent
Cable flexibility
Rigid

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Operating temperature, range
-25 ... 60 °C
Flame retardant
C2, NF C 32-070
Weather resistance
Very good
Chemical resistance
Accidental
Water proof
Intermittent
Minimum static operating bending radius
340 mm
Packaging
-

Resources

Resources

Documentation

PEP ARVFV pdf — 4.1 MB

Declaration of Performance

  • Declaration of Performance n� : 1000016-FRJE
  • Certification Date : 11/29/16
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : NB 1812
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close