Nexans U-1000 R2V C1 5G6

Description

Description

Standards

  • Product
    IEC 60228; NF C32-013; NF C32-013
  • Test
    NF C32-070/C1; NF C32-070/C1

Applications

These power and control cables are used for electricity supply in low voltage installation system. They are well adapted to underground use in industrial applications with an additional mechanical protection. These cables can be fixed on cable trays, within conduits or fixed to walls. They are fire retardant.

 

Design

Conductor:

Stranded bare copper or aluminium

Insulation

Cross-linded polyethylene (XLPE)

Sheath or tape:

Optional

Outer sheath:

Polyvinyl chloride (PVC)

 

Core indentification

According to HD 308 S2 or printed number with or without green/yellow
 

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2
Insulation
XLPE (Cross-linked Polyethylene)
Outer sheath
PVC
Sheath colour
Black
With Green/Yellow core
Yes
Conductor material
Bare copper
Conductor shape
-

Dimensional characteristics

Dimensional characteristics

Number of cores
5
Conductor cross-section
6 mm²
Minimum outer diameter
15.1 mm
Maximum outer diameter
16.6 mm
Approximate weight
498 kg/m

Electrical characteristics

Electrical characteristics

Permissible current rating in open air
45 A
Permissible current rating when buried
55 A
Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Fire retardant
NF C 32-070 C1
Operating temperature, range
-20 ... 60 °C
Bending factor when installed
6 (xD)
Max. conductor temperature in service
90 °C

Resources

Resources

Selling & delivery Information

Current rating in Amperes according to NF C 15100 for ambiant temperature :

30 ° C (in open air)

20 ° C (underground)

Declaration of Performance

  • Declaration of Performance n� : 1000238-FRME
  • Certification Date : 12/1/16
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : NB 1812
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*