Nexans U-1000 R2V DISTINGO NX'TAG™ 5G2.5 R100m

Description

Description

Standards

  • Product
    IEC 60502-1; NF C32-321

Avantages

These U-1000 R2V cables with XLPE insulation and PVC outer sheath can be used in all low voltage power installations. Multiconductors cables are adapted to remote control and telecontrol installations.

It could be installed outside without protection (UV resistance, AN3 according to NF C15-100)

The Nexans U-1000 R2V cable family consists of :

  • The Nexans U-1000 R2V DISTINGO NX'TAG range, manufactured in France, for 1.5 and 2.5mm2 cross-sections, from 3 to 5 conductors, with the same characteristics. A marking zone identifies each cable and its destination during installation.
  • The Nexans U-1000 R2V DISTINGO range, also manufactured in France, for cross-sections between 6 and 16mm2, from 1 to 5 conductors. The Nexans U-1000 R2V range in MOBIWAY MOB packaging.
  • And the Nexans U-1000 R2V range, for cross-sections from 25mm2 upwards.

The Nexans U-1000 R2V DISTINGO cable makes life easier on site: clever markings make it possible to identify the cross-section, the number of conductors and the remaining length on the reel at a glance.

Advantages of the Nexans U-1000 R2V DISTINGO range :

  • Metric marking to identify the remaining cable length
  • Direct identification of the cross-section on the cable and on the packaging
  • UV resistance
  • Nexans quality
  • Available in Mobiway MOB

Installation

These cables can be fixed on cable trays, within conduits or fixed to walls, installed outside. They also can be buried directly with extra mechanical protection.

Permissible current and voltage drop are given

a) in free air, sheltered from sun, on cable tray or bracket, on cable ladder, and spaced from the wall, temperature = 30°C.
b) buried with thermal resistivity of the ground 1Km/W, laying depth : 600 mm, temperature = 20°C.

If conditions are differents, apply correction factors from NF C 15-100 standard  or equivalent national standard

Voltage drop

Calculated with cosj = 0,8

Marking

S.Y. + NF - USE Factory n°  U-1000 R2V n (x or G) s mm²

  • n = number of cores
  • s = section in mm²
  • G = with Green-Yellow
  • x = without Green-Yellow

For DISTINGO™, metric marking METRIUM™

·         For packed drums, the length can be directly read
·         For coil and other drums (from cut to length), remaining length is easily calculated. For coil, make the difference between external and internal extremity; for drums make the difference between indication on sticks and external extremity.

Les + de la gamme Nexans U-1000 R2V DISTINGO NX'TAG

For each cross-section, a colour

Available in MOBIWAY MOB drum

Distingo RANGE

Tirage sur les conducteurs des câbles

Lors du tirage des câbles, tous les conducteurs participent à l'effort de manière identique. La force maximale de traction ne doit en aucun cas dépasser 5 daN/mm² de section globale (1.5 et 2.5mm²).

Nexans EasyCalc, l'outil gratuit de calcul de section de câble

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Solid class 1
Conductor material
Bare copper
With Green/Yellow core
Yes
Insulation
XLPE
Outer sheath
PVC
Sheath colour
Black
With smaller neutral conductor
No
Conductor shape
Circular
Lead free
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
5
Conductor cross-section
2.5 mm²
Approximate weight
200 kg/km
Maximum outer diameter
14.5 mm
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Max. DC resistance of the conductor at 20°C
7.41 Ohm/km
Permissible current rating in open air
31 A
Permissible current rating when buried
41 A
Voltage drop, 3 conductors
13.2 V/A.km
Voltage drop, single phase
- V/A.km

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
-
Cable flexibility
Rigid

Usage characteristics

Usage characteristics

Range
DISTINGO NX TAG
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Operating temperature, range
-25 ... 60 °C
Flame retardant
C2, NF C 32-070
Weather resistance
Good
Chemical resistance
Accidental
Water proof
Intermittent
Packaging
Coil
Length
100 m
Laying operation bending radius
174 mm
Minimum static operating bending radius
87 mm
U.V resistance
AN3

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000205-FRAU
  • Certification Date : 6/29/21
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : NB 1812
  • Declared performance : Eca

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error