EN 50288-7 Silicone IOS Armoured LC 30x2x1,5

Description

Description

Standards

  • Test
    IEC 60331; IEC 60332-3-22 Cat.A

Applications

 

These instrumentation and communication cables are used to transmit analogue or digital signals in measurement and process control. They are well adapted to underground use in industrial applications, in moist areas, where hydrocarbon and mechanical protection are needed. The lead cover brings an enhanced resistance to aromatics hydrocarbons. The individual screening of each pair limits the consequence of crosstalk. They maintain circuit integrity when exposed to fire.

 

Design

Conductor:

Stranded bare copper class 2

Insulation:

Silicone rubber (Sil)

Individual screen

Polyester tape

Tinned copper drain wire 

Aluminium backed polyester tape

Polyester tape

Overall screen

Polyester tape

Tinned copper drain wire 

Aluminium backed polyester tape

Inner sheath:

Low Smoke Zero Halogen (LSZH)

Colour: black

Lead sheath:

Bedding (intermediate sheath):

Polyvinyl chloride (PVC)

Colour: black

Armour:

Galvanized steel wires (SWA)

Outer sheath:

Polyvinyl chloride (PVC)

Colour: black

Other colour on request.

 

Core identification

Pair: white - black
White core printed with pair number
 

 

Marking

NEXANS 279 SIL/IND.+OA.SCR/LSZH//LC/PVC/SWA/PVC 170/300V Nber of pairs & cross-section Cu IEC 60331 IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

EN 50288-7 (Design guide-lines)

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Bare copper
Type of conductor
Stranded, class 2
Insulation
Silicone rubber
Individual screen
Tinned copper drain wire + aluminium/polyester tape
Overall screen
Tinned copper drain wire + aluminium/polyester tape
Inner sheath
Low smoke, zero halogen thermoplastic compound
Lead Sheath
Yes
Intermediate sheath
PVC
Armour type
Galvanized steel wires
Outer sheath
PVC
Protection
Yes

Dimensional characteristics

Dimensional characteristics

Number of pairs
30
Conductor cross-section
1.5 mm²
Conductor diameter
1.5 mm
Diameter over insulation
2.66 mm
Diameter over inner sheath
35.1 mm
Diameter over lead sheath
38.3 mm
Diameter over intermediate sheath
41.1 mm
Diameter over armour
45.1 mm
Minimum outer diameter
44.6 mm
Maximum outer diameter
52.0 mm
Approximate weight
6033 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
170/300V

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Fire resistant
IEC 60331
Fire retardant
EN IEC 60332-3-22 (cat A)
Chemical resistance
Aliphatic and aromatic hydrocarbons resistant
Electro magnetic interference resistance
Yes
Operating temperature, range
-20 ... 60 °C
Max. conductor temperature in service
90 °C
Standard
EN

Resources

Resources

Selling & delivery Information


Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.


Minimum bending radius:

10 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close