74C068 SH MT 6/6kV ... K3 NA
74C068 SH MT 6/6kV ... K3 NA
- Medium voltage cables 6/6 (7.2) kV
- CST 74C068
- Zero halogen (SH)
- Cables installed outside of the containment area (K3)
- Unarmoured (NA)
74C068 SH MT 6/6kV 3x50 Cu2 K3 NA
Nexans ref.
- Packaging: Cut to length (m)
- Conductor material: Plain copper
- Conductor cross-section: 3 mm²
- Number of cores: 50
74C068 SH MT 6/6kV 3x50 Alu2 K3 NA
Nexans ref. 10215352
- Conductor material: Aluminum
- Conductor cross-section: 50 mm²
- Number of cores: 3
74C068 SH MT 6/6kV 3x150 Alu2 K3 NA
Nexans ref. 10215353
- Conductor material: Aluminum
- Conductor cross-section: 150 mm²
- Number of cores: 3
74C068 SH MT 6/6kV 3x185 Alu2 K3 NA
Nexans ref. 10215351
- Packaging: Cut to length (m)
- Conductor material: Aluminum
- Conductor cross-section: 185 mm²
- Number of cores: 3
74C068 SH MT 6/6kV 3x240 Alu2 K3 NA
Nexans ref. 10216539
- Conductor material: Aluminum
- Conductor cross-section: 240 mm²
- Number of cores: 3
Description
Description
Standards
-
ProductIEC 60228; IEC 60502-2
-
TestIEC 60332-3-23; IEC 60754-1; IEC 61034-2; NF C32-070/C1; NF C32-070/C1
Applications
These medium voltage cables are used for medium voltage power supply,
Design
Conductor:
Stranded bare copper or aluminium (class 2)
Screen:
Semi-conductor
Insulation:
Ethylene Propylene Rubber (EPR)
Assembling sheath:
Halogen free
Inner sheath:
Halogen free
Screen:
Semi-conductor
Copper tape
Outer sheath:
Low smoke, zero halogen (LSZH)
Colour: Black
Core identification
3x: natural cores printed with black numbers
Marking
NEXANS 279 Nber of cores & cross-section Cu/Al CST 74 C 068 00 K3 SH 6/6(7.2) kV YYYY Manufacturing number + metric marking
Standard
IEC 60332-3-23(B)
Quality insurance according ot RCC-E
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Selling & delivery Information
Minimum bending radius:
8 x outer diameter
To be doubled during laying operations